- Assign the variable to a memory address (%MW).
- Tick "Save" in data properties for this variable.
- Ensure in the CPU configuration that "Initialize %MW1 on cold start" is unticked and that "Automatic start in Run" is ticked.
- Assign the variable to a memory address (%MW).
- Tick "Save" in data properties for this variable.
- Ensure in the CPU configuration that "Initialize %MW1 on cold start" is unticked and that "Automatic start in Run" is ticked.
- Simulation code for Rockwell (simulation_routine_ST.L5X called before the PID routine):
- Schneider's M580 CPUs have Modbus TCP enabled by default.
- On Control Expert, assign the variable a memory address (e.g., IO_INT, data type INT, memory address %MW10).
- On TIA Portal use the block MB_CLIENT to communicate via PROFINET as Modbus TCP Client.
- Switch: MCSESM083F23F1 Modicon Extended Managed Switch, 8 ports for copper
- Download and install SoMove.
- When launching SoMove click on the popup for the activation. From the Schneider website download the license file.
- Place the license file (.lic) in the folder: C:\Program Files (x86)\Common Files\Schneider Electric Shared\LicenseFiles
There are different sizes of Schneider Control Expert licenses, S, L, L safety, XL, XL safety.
- Open TUV's Certipedia website.
- Search by manufacturer, e.g., Schneider Electric.
- Refine the results from the previous search, e.g., Model Name M580.
- Open the appendixes and review software and firmware versions.
- Set the rotary switch at the back of the CPU (see #10 below), in order to have one CPU as A and the other as B.
- The trick to trigger a soft starter that is wired in line with a TeSys Island starter, is to send the run command to both of them at the same time.
For example: Supply MCB > TeSys DOL (TPRSS025) > ATS01 Soft Starter (ATS01N125FT) > 3 Phase Motor.
The first thing to do is check the current Libset version (right-click in Project):
In the TPRBCEIP Bus Coupler there are different LED Status that are helpful for troubleshooting:
- Export the following files from the Managed Switch:
- Knowing the IP address of the License server open "License Manager" in the VM:
Right-click on "Derived FB Types" and "Get from Library":
There are different system words that help the troubleshooting:
Link to the Modicon Libraries (GPL for Control Expert, AVEVA OMI, etc).
Check the latest firmware version at Schneider's website:
Check the compatibility of the profiles with the switch (reference document: System Guide Hardware in a Complex M580 System):