#220 - AVEVA Changes on GPL attributes

On the GPL there are some attributes that can be changed:

- Motor, MotorVS, DValve: Param.ModeNormal: set as P. So when the device is placed in Operator mode, an orange icon will appear and the letter "O".

- SDDevCtl.St.Rearm (VFD) / DevCtl.St.Rearm (DOL): change from secured writable to operate to remove the rearm confirmation window.

- Update priority of alarms: Edit values on CSV export for each device, from 250 to 999 and edit the text description to match the alarm.

- GPL_Faceplate: Choose True or False in order to have the pop-up fixed or not.

- Param.HiOP, HiPV: To increase the max. speed in MotorVS.