The Actuator Sensor Interface
(ASi) protocol has existed since 1999 and is still widely used in industrial
environments, logistics centers and others. Some of the main advantages are the
relatively low cost of the systems and the facility to replace devices.
In this post we will make a
brief introduction to this protocol with some practical examples. The communication is the serial type, between an
AS-i Master module and AS-i Slaves. Using a Siemens ET200SP CPU a possible
hardware configuration is shown below. In this case, the AS-i modules are part
of the CM (Communication Module) series product group.
In the field, the AS-i slave
standard and safety modules (normally identified with yellow color) are
installed. The connectors are usually M12. The addressing is done with an
external device that is inserted in the ADDR port. The address of a standard module is divided into two (A
and B) and the safety module has a single number. For example the standard
module could have address # 14A (or # 14B) and the safety module # 12. When
replacing a defective module, AS-i Master recognises the new module and
automatically reconfigures it.
The two cables responsible for
exchanging data between the AS-i modules are inside the yellow protection /
insulation below, one for AS-i + positive control signals and one for AS-i-
negative signals . In addition, these two cables inside the yellow protection
also make the power supply of the slave modules and IOs in the field, normally
the positive power is + 30VDC or + 24VDC and the negative 0V. The two cables
inside the black protection, make an auxiliary power supply to the actuators.
The teeth behind the modules ensure the connection between the modules and the
cables.
Typical applications are
digital or analog inputs and outputs and safety inputs as emergency
pushbuttons. The cable distance above can be up to 100m for 30VDC systems, and
50m for 24VDC systems. There are repeaters that can be added for greater
distances. In addition, good practices should be applied for the installation
of AS-i network cables in the field, such as respecting the distances between
them and the factory power cables, avoiding cable loops, installing
terminations correctly and module grounding and trays in the field. These
points are particularly critical for safety signs.
In the first image of the
post, the AS-i Master is connected to the same "backplane" as the
PLC. However, there are also options for AS-i Master modules that are Gateway
and communicate with the networked PLC as Profinet or Ethernet-IP.
No comments:
Post a Comment