#323 - Rockwell How to integrate a PowerFlex VFD into Studio5000

- Carry out the drive configuration in CCW and then import the settings from Studio5000.

Note: For CCW download the files and launch the "23.00.00-CCW-INT-Std-DVD.part1.exe" application. After launching the application launch the "Setup.exe" inside the "23.00.00-CCW-INT-Std-DVD" folder.

Configuration from the Drive's display:

- Factory Reset: Navigate to Basic Program group P and select P053 > 2 (enter) for a factory reset. Reset (Red Button O) the Fault F048 that will appear.

- Setup the IP address: Navigate to Parameters group C (Comms) and edit the following parameters:

C128: Set to 1 (instead of BOOTP default 2).

C129, 130, 131, 132: Set the IP octets (e.g., 192, 168, 0, 10).

C133, 134, 135, 136: Set the subnet octets (e.g., 255, 255, 255, 0).

Power cycle the drive and test comms to the drive.

Configuration through CCW:

- Click on Discover and connect to the drive through its IP address.

- Click on Add to project.

- Click on Wizards and launch the start wizard.

Enter these motor faceplate details: Voltage, Frequency, FLA, Speed, Power, OL, Motor Poles.

- Jog the motor from CCW.

- Note that CCW uses RSLinx Classic to communicate with the drive. Here below is how to add a target IP in RSLinx Classic:

Configuration in Studio5000:

- Setup the EtherNet/IP mode for Start, Stop, Reset, and Speed Reference, i.e., parameters 46 (Start Source 1) and 47 (Speed Reference 1).

- Add a new module to the dedicated ethernet branch (A1 or A2).

- Choose the correct power flex module (e.g., 525-EENET).

- Assign the IP address and upload the drive.

- Control through the native IO Tags:

Pump:O.Start, Pump:O.Stop : To start the drive set Start to 1 and Stop to 0, and to stop the drive set Start to 0 and Stop to 1, then back to 0. 

Pump:O.FreqCommand : Scaled by 100, e.g., 10Hz = 1000.

- Data Links can be added (up to 4 commands and 4 status).

Go offline > Drive Overview > Device Definition > Connection Format > Input / Output (from PLC perspective). Close the window and download the configuration to the drive.

- Logic: 

:O.START := RUN_CMD AND NOT :I.FAULTED AND NOT :I.ACTIVE AND :I.READY;

:O.STOP := NOT :O.START;

IF :I.ACTIVE THEN :O.FREQCOMMAND := 60 * 100;

ELSE :O.FREQCOMMAND := 0;

:O.CLEARFAULTS := RESET;