- Carry out the drive configuration in CCW and then import the settings from Studio5000.
Note: For CCW download the files and launch the "23.00.00-CCW-INT-Std-DVD.part1.exe" application. After launching the application launch the "Setup.exe" inside the "23.00.00-CCW-INT-Std-DVD" folder.
Configuration from the Drive's display:
- Factory Reset: Navigate to Basic Program group P and select P053 > 2 (enter) for a factory reset. Reset (Red Button O) the Fault F048 that will appear.
- Setup the IP address: Navigate to Parameters group C (Comms) and edit the following parameters:
C128: Set to 1 (instead of BOOTP default 2).
C129, 130, 131, 132: Set the IP octets (e.g., 192, 168, 0, 10).
C133, 134, 135, 136: Set the subnet octets (e.g., 255, 255, 255, 0).
Power cycle the drive and test comms to the drive.
Configuration through CCW:
- Click on Discover and connect to the drive through its IP address.
- Click on Add to project.
- Click on Wizards and launch the start wizard.
Enter these motor faceplate details: Voltage, Frequency, FLA, Speed, Power, OL, Motor Poles.
- Jog the motor from CCW.
- Note that CCW uses RSLinx Classic to communicate with the drive. Here below is how to add a target IP in RSLinx Classic:
Configuration in Studio5000:
- Setup the EtherNet/IP mode for Start, Stop, Reset, and Speed Reference, i.e., parameters 46 (Start Source 1) and 47 (Speed Reference 1).
- Add a new module to the dedicated ethernet branch (A1 or A2).
- Choose the correct power flex module (e.g., 525-EENET).
- Assign the IP address and upload the drive.
- Control through the native IO Tags:
Pump:O.Start, Pump:O.Stop : To start the drive set Start to 1 and Stop to 0, and to stop the drive set Start to 0 and Stop to 1, then back to 0.
Pump:O.FreqCommand : Scaled by 100, e.g., 10Hz = 1000.
- Data Links can be added (up to 4 commands and 4 status).
Go offline > Drive Overview > Device Definition > Connection Format > Input / Output (from PLC perspective). Close the window and download the configuration to the drive.
- Logic:
:O.START := RUN_CMD AND NOT :I.FAULTED AND NOT :I.ACTIVE AND :I.READY;
:O.STOP := NOT :O.START;
IF :I.ACTIVE THEN :O.FREQCOMMAND := 60 * 100;
ELSE :O.FREQCOMMAND := 0;
:O.CLEARFAULTS := RESET;