#300 - Rockwell How to setup the IP address on a CompactLogix/ Compact 5000 IO through BootP DHCP

- Open BootP DHCP and select the NIC that will be the DHCP Server.

- Check the MAC on the device and enter both the MAC and the desired IP address.


- Ping the new IP to validate.

- On the bottom screen, click on Disable BOOTP/DHCP so that the PLC will retain the configured IP address after power cycle and test the ping again.

- Note that some CompactLogix CPU have 2 RJ-45 ports and each one of them has its own MAC address. In Studio5000 it is possible to select the desired configuration for these ports, i.e., Dual-IP or DLR. However if an error occurs when changing this configuration and downloading to the CPU via ethernet cable, use the USB connection to download it.

- To edit the CPU's IP address, open FT Linx from Studio 5000 and click on the CPU's spanner to edit its network configuration (IP, gateway, etc).


- Notes: For the Compact 5000 IO, setup the PC in static IP mode in the 192.168.1.x range, then open BootP DHCP and wait the Compact IO MAC address to be displayed.
Open FactoryTalk Linx Network Browser and add the static IP of the Compact 5000 IO that was previously set. It's then possible to edit the IP and the subnet range as desired.