July 19, 2025

#260 - Troubleshooting a Stratix Switch

- The easiest way to configure a Stratix switch (e.g., Stratix 5200) is through the Express setup.

- Remove all the cables to the switch and power on and wait for the boot process to complete.

- When the EIP and MOD status start flashing green, press and hold the Express Setup button for about 5 seconds (until the Express Setup LED blinks) to activate this mode of configuration with an external PC.

- Connect the PC to the flashing port with the PC configured in DCHP mode to get an IP address in the 192.168.1.x range. Check DHCP server managed to write address by typing ipconfig /all command.

- Open the web browser at the default web address: 192.168.1.254 (login: admin/ password: switch).

- Follow the screens to complete the configuration, for example setup the user/passwords, device name (e.g., KFE01), VLAN ID (change from default 1 if needed), static IP and subnet.

- Download the latest available firmware on the Rockwell's Compatibility Website and install it through the web browser. From the
Administration menu, select Software Upgrade and in Upgrade Mode choose INSTALL from the drop-down menu.

- Assign the smart ports depending on the roles (Configuration > Layer 2 > Smartports) and Save the configuration (changes are not automatically saved):



- Smart Port assignment examples:
Automation Devices: RIO, VFD, PLC, etc.
Multiport Automation Device: Unmanaged Switches (e.g., Stratix 2000), or if devices are unknown.
Switch for Automation: Managed Switches (e.g., Stratix 5700, 5200, 5400).
- Mirroring a port and analysing it in wireshark can be useful for troubleshooting. To set up a mirror source and destination ports, in the web browser go to Configuration > Layer 2 > SPAN and then click on Add.

No comments: