- Restore the project and make it active:
- Include the SGC_Include2 project in the include tab:
- Pack the project and the included projects:
- Launch the setup wizard to ensure all services are running (Client, IOServer, Alarm, Trend and Report):
Note: Select Server and Control Client with Multi-Process enabled.
- Edit the computer parameters to run in localhost (127.0.0.1) during development:
- Add new PLC in the I/O device tab:
Note: This option is the Linked IO Device method. A link icon will appear next to the added IO Device.
Sometimes when launching the Runtime the connection to the PLC is established after the error message box is clicked Ok: Error Cannot find file <Citect>\Bin\SIXSTSR.DLL: error = 126.
- In Citect Graphics Builder create the new screens with the same name as the ones to be imported.
- Copy and paste the files in the project folder:
- Pack, compile and open each modified page.
- Save the pages and run the project.