To import the GPL in Citect follow these steps:
- Create the Tag in PLC:
Example of DINPUT tag: NC10_BS_DINPUT
Create the DINPUT_ST tag: NC10_BS_DINPUT_ST, and enable its HMI

- Add the PLC (IO device) in the project
- Edit the auto imported tags by adding the char 'W' as a suffix. Note that it adds the device name set in the OFS as a prefix (e.g. M580_).
- In the graphics, create a new instance of SGC_dinput Genie with this tag: M580_NC10_BS.
- Edit these two .DBF files that are in the project folder (C:\ProgramData\AVEVA\Citect SCADA 2018 R2\User\MyProject):
ADVALM.DBF
VARIABLE.DBF
Open them in Microsoft Access, edit the fields, save as DBFIII.