June 26, 2024

#213 - Schneider configuration of the PLC Simulator to connect to the ASP MCS

- Connect to the PLC Simulator and download a project file

- Change the default settings from:

Listening IP: 127.0.0.1 to 0.0.0.0

- Edit the configuration file: IPSimPortAssign.xml ( C:\Users\Admin\AppData\Local\Temp\IPSimPortAssign.xml)

<EquiList> <PLCAdressSim Address="10.2.0.62" Port="502"/> </EquiList>

Note: This is the same IP as the PC.

In MCS: Set the same IP (e.g. 10.2.0.62) and restart the service.

Example:

Ensure the IP of the SIM running instance is the same as in MCS:
Note: if the MCS configuration web-page inside OCMC does not open, restart the services: MCS Configuration Service and MCS UI Service.